Testing directional time-overcurrent protection in ring networks
Testing directional time-overcurrent protection in ring networks
Equipment set for directional time-overcurrent protection: students set pick-up values, tripping times and the characteristic angle and check selectivity with power flowing in both directions.
- Explaining function and areas of application
- Parameterizing the protective relay
- Determining the inherent system operating time
- Checking the selectivity of direction detection
- Detecting power flow direction
- Parameterization via SCADA or directly on the device
- Creating short circuits safely
- Flexible tripping characteristics
In meshed networks and loop circuits, simple time-overcurrent protection is not sufficient for selective disconnection. Directional protection also detects the direction of power flow: the relay uses current, voltage and phase angle to determine whether the fault lies upstream or downstream of the measuring point. The equipment set replicates a line section with a line model, circuit breaker, variable load and variable three-phase power supply. Students set pick-up values, tripping times and the characteristic angle, either via the front panel buttons or on the PC via RS485. They create specific short circuits, record the inverse-time tripping characteristic and determine the inherent operating time of the protection system for different fault types.
| Base Product | |
| CO3301-4D | Time Overcurrent Relay with directional feature |
| CO3301-5N | Relay Test Unit |
| CO3301-3A | Transmission line Model 150km/300km (93.2miles/186.4miles) |
| CO3301-3F | Variable Ohmic load, three-phase, 1kW |
| CO3301-5P | Power switch module |
| SO2800-6L | Interactive Lab Assistant: Protective systems for high-voltage transmission line |
| Software | |
| SO4001-3H | Software SCADA Viewer |
| Power Supply | |
| CO3301-3Z | Adjustable 3-phase power supply, 0-450V/2A |
| Measuring Instruments | |
| CO5127-2S | Power Quality Meter mit Grafikdisplay und Langzeitspeicher |
| LM2330 | Multi13S digital multimeter |
| Accessories | |
| LM9057 | Patch cable Cat5E 1x 1m yellow, 2x 2m yellow |
| LM8257 | USB 2.0 Ethernet adapter, 10/100 |
| LM9988 | 5-Port Ethernet Switch |
| ST8010-4J | Multiple socket outlet, 6 fold, with illuminated switch |
| LM9025 | Interface converter USB/RS485 |
| Furniture | |
| ST7200-7A | SybaPro experiment trolley, 3-level, 6 sockets, 1250x1970x800mm |
| ST8010-4T | Monitor holder for flat screen monitor of weight up to 15kg / 33lbs |
| ST7200-5L | Protection cover for three-level experiment trolleys |
| ST8010-4G | Keyboard adapter for flat screen monitor holders |
| Furniture Accessories | |
| ST8000-4L | Display for Power Transmission equipment |
| Measurement Leads | |
| SO5126-3R | Safety connecting plug 4mm with tap (2x), black, 1000V/32A CAT II |
| SO5126-3V | Safety connecting plug 4mm with tap (2x), blue, 1000V/32A CAT II |
| SO5126-3W | Safety connecting plug 4mm with tap (2x), green/yellow, 1000V/32A CAT II |
| SO5148-1L | Set of safety measurement cables, 4mm (31 leads) |
Learning Content in Detail
Explaining function and areas of application
Parameterizing the protective relay
Determining the inherent system operating time
Checking the selectivity of direction detection
Recording the tripping characteristic
Features & Applications
- Detecting power flow direction — The relay distinguishes between faults in the forward and reverse directions. This allows it to be used selectively in loop circuits.
- Parameterization via SCADA or directly on the device — The relay can be set either by hand using the front panel buttons or on the PC via the RS485 interface.
- Creating short circuits safely — Students deliberately trigger short circuits and use them to test the tripping stages of the relay. Users and equipment remain protected.
- Flexible tripping characteristics — The relay operates as definite-time (DMT) or inverse-time (IDMT) overcurrent protection with normal inverse, very inverse or extremely inverse characteristics.
- Directional time-overcurrent relay (CO3301-4D) — This digital relay has an adjustable relay characteristic angle (RCA) and an RS485 interface.
- Line model 150 km / 300 km (CO3301-3A) — This three-phase model of an overhead line at a scale of 1:1000 allows realistic analyses of operation and faults.
- Circuit breaker module (CO3301-5P) — The module switches the voltage on and off by remote control during simulated short circuits and indicates its status.
- Variable resistive load (CO3301-3F) — Synchronously adjustable toroidal rheostats simulate loads in wye or delta connection.
- Variable three-phase power supply 0–450 V / 2 A (CO3301-3Z) — This infinitely variable power supply with variable transformer and motor protection circuit breaker supplies the system safely.
- SCADA Viewer — The software controls and parameterizes the relay and records the tripping behavior and inherent system operating time in real time.

From Knowledge Comes Capability.
You guide the learning
Where theory and practice go hand in hand.
RXLea brings a new way of learning: project-based, hands-on and clearly structured. Learners solve real-world tasks, while instructors save time on preparation. Interactive modules, smart analytics and real hardware create a modern, efficient learning world.
Hands-on and interactive
Animations, interactive tasks and realistic scenarios build a deep understanding. All content is organized into clear learning paths for focused, hands-on learning.
Digital support
3D assembly animations and digital instructions simplify complex procedures, reduce errors and help learners work more independently.
Visual support
Overview graphics, screenshots and sample animations make the learning world transparent. Photos from the learning packages are also available, including country-specific versions where needed.