Generator Differential Protection
Generator Differential Protection
Equipment for strictly selective unit protection: participants parameterize a digital three-phase current differential protection relay and demonstrate when it trips and when it remains stable.
- Calculating the basic parameters of the protected object
- Demonstrating stability during an external short circuit
- Measuring the minimum pick-up current
- Testing selectivity with a two-phase fault
- Replicating extensive protected zones on a single training panel
- Exploring current transformer saturation and characteristic stabilization
- Scaling data from large installations to safe laboratory values
- Switching from generator to transformer differential protection
An internal fault in a generator must be cleared instantaneously, otherwise severe damage will result. Differential protection achieves this as absolutely selective protection: it compares the currents in magnitude and phase angle at two separate measuring points, on the neutral-point side and on the outgoing side, and uses this to determine the location of the fault. The equipment brings this widely spaced arrangement together on a single training panel. Using bridging plugs, participants inject faults either inside or outside the current transformer boundaries, edit the tripping characteristic via the tripping current and restraint current, and investigate how false tripping due to current transformer saturation is suppressed.
| Base Product | |
| CO3301-4M | Transformer / Generator differential protection relay |
| CO3301-5W | Multifunktionsrelais, Leistungsregler, cos-phi Regler, Synchronisiergerät |
| SO2800-3U | Interactive Lab Assistant: Generator protection |
| SE2682-5Q | Three-phase synchronous machine with smooth core rotor, 1kW |
| CO3301-5G | Exciter voltage controller with de-excitation |
| CO3212-1P | Motor protection switch, 3 pole, 1.8-2.5A |
| CO3301-5L | HMI (Human Machine Interface) for generators |
| CO3301-3F | Variable Ohmic load, three-phase, 1kW |
| Software | |
| SO4001-3H | Software SCADA Viewer |
| Power Supply | |
| CO3212-5V | Three-phase power supply with motor protection switch |
| Accessories | |
| LM9057 | Patch cable Cat5E 1x 1m yellow, 2x 2m yellow |
| LM8257 | USB 2.0 Ethernet adapter, 10/100 |
| LM9988 | 5-Port Ethernet Switch |
| ST8010-4J | Multiple socket outlet, 6 fold, with illuminated switch |
| CO3636-6Y | Servo machine test stand for 1kW machines incl. software ActiveServo (D,GB,F,E) |
| SE2662-7D | Coupling guard with LED lighting for 1kW machines |
| SE2662-6A | Rubber coupling sleeve, 1kW |
| Furniture | |
| ST7200-7A | SybaPro experiment trolley, 3-level, 6 sockets, 1250x1970x800mm |
| ST8010-4T | Monitor holder for flat screen monitor of weight up to 15kg / 33lbs |
| ST7200-5L | Protection cover for three-level experiment trolleys |
| ST8010-4G | Keyboard adapter for flat screen monitor holders |
| ST8008-8N | Protected power distribution for working stations |
| ST8010-4J | Multiple socket outlet, 6 fold, with illuminated switch |
| Furniture Accessories | |
| ST8000-4J | Display for Power Generation equipment |
| Measurement Leads | |
| SO5126-3R | Safety connecting plug 4mm with tap (2x), black, 1000V/32A CAT II |
| SO5126-3V | Safety connecting plug 4mm with tap (2x), blue, 1000V/32A CAT II |
| SO5126-3W | Safety connecting plug 4mm with tap (2x), green/yellow, 1000V/32A CAT II |
| SO5148-1L | Set of safety measurement cables, 4mm (31 leads) |
Learning Content in Detail
Calculating the basic parameters of the protected object
Demonstrating stability during an external short circuit
Measuring the minimum pick-up current
Testing selectivity with a two-phase fault
Features & Applications
- Replicating extensive protected zones on a single training panel — The spatially separated current transformer measuring points on the neutral-point side and outgoing side are replicated compactly. Using bridging plugs, participants inject faults inside or outside the notional current transformer boundaries.
- Exploring current transformer saturation and characteristic stabilization — The relay’s tripping characteristic can be freely edited and tested. Participants work directly with the tripping current and restraint current variables.
- Scaling data from large installations to safe laboratory values — Linked parameter files scale real large power plant data down to 520 VA and 400 V. Participants work with the ratios of real installations without needing their power in the laboratory.
- Switching from generator to transformer differential protection — The equipment can be reconfigured for three-phase transformer differential protection, including vector group compensation such as Dyn5 and suppression of the inrush current. Additional modules are required for the transformer protection experiments.
- Differential protection relay CO3301-4M — The industrial protection device has 14 freely definable LEDs, a graphic display and a native Modbus TCP/IP interface.
- Excitation voltage controller CO3301-5G with de-excitation switch — The controller supplies 7.5 to 200 V at a maximum of 2 A and automatically de-excites the generator in the event of a fault.
- Four-quadrant test bench CO3636-6Y — The test bench operates statically and dynamically in four quadrants and provides ten driven machine models, including a fan, a pump and a time-dependent load.
- Multifunction relay CO3301-5W — The freely parameterizable relay digitally monitors generator and grid parameters, features alarm class logic and combines control, protection and automatic synchronization.
- Industrial software for parameterizing the differential protection — The operating and parameterization software manages protection architectures via a tree structure and is connected via Ethernet. Participants read out data, change parameters online and work with the hierarchical password management up to supervisor level 3.
- Industrial software for the multifunction relay — The menu-driven configuration software is connected via USB. Participants observe the measured values in real time and link digital signals.
- SCADA Viewer — The software displays currents, line voltages, power values and device states synchronously on screen. Using the logger, participants record transient measured variables over time and export the charts to verify selectivity.

From Knowledge Comes Capability.
You guide the learning
Where theory and practice go hand in hand.
RXLea brings a new way of learning: project-based, hands-on and clearly structured. Learners solve real-world tasks, while instructors save time on preparation. Interactive modules, smart analytics and real hardware create a modern, efficient learning world.
Hands-on and interactive
Animations, interactive tasks and realistic scenarios build a deep understanding. All content is organized into clear learning paths for focused, hands-on learning.
Digital support
3D assembly animations and digital instructions simplify complex procedures, reduce errors and help learners work more independently.
Visual support
Overview graphics, screenshots and sample animations make the learning world transparent. Photos from the learning packages are also available, including country-specific versions where needed.