Basic Generator Protection Equipment Set

EGP11PT

Basic generator protection equipment: on a digital multifunction relay, participants set up overvoltage and undervoltage, overcurrent, unbalanced load, reverse power and stator ground fault protection for a synchronous generator.

Learning Content
  • Parameterizing overvoltage and undervoltage protection
  • Analyzing time-overcurrent protection
  • Testing unbalanced load protection
  • Setting reverse power protection
KEY FEATURES
  • Covering thermal and electrical generator faults
  • 1 kW power class with limited generator current
  • Multifunction relay CO3301-5W
  • Excitation voltage controller CO3301-5G with de-excitation switch
Speak with a Product Specialist +1 (757) 808-5696 · sales@lucas-nuelle.com

A generator’s winding insulation and mechanical components can only withstand grid-side and internal overstress if coordinated protection functions monitor them continuously. This basic equipment set replicates generator protection on a laboratory scale: an industry-standard multifunction relay monitors generator and grid parameters in accordance with the ANSI standard, the four-quadrant test bench supplies the drive torque, and the excitation voltage controller provides the excitation, including automatic de-excitation. Participants bring about critical operating states, from grid synchronization to fault conditions, and record and evaluate them by measurement. They configure the protection parameters themselves and then validate the automatic disconnection from the grid, including rapid de-excitation.

CO3301-5WMultifunktionsrelais, Leistungsregler, cos-phi Regler, Synchronisiergerät
SO2800-3UInteractive Lab Assistant: Generator protection
SE2682-5QThree-phase synchronous machine with smooth core rotor, 1kW
CO3301-5GExciter voltage controller with de-excitation
CO3212-1PMotor protection switch, 3 pole, 1.8-2.5A
CO3301-5LHMI (Human Machine Interface) for generators
CO3301-3FVariable Ohmic load, three-phase, 1kW
CO3212-5VThree-phase power supply with motor protection switch
SO4001-3HSoftware SCADA Viewer
LM9057Patch cable Cat5E 1x 1m yellow, 2x 2m yellow
LM8257USB 2.0 Ethernet adapter, 10/100
LM99885-Port Ethernet Switch
ST8010-4JMultiple socket outlet, 6 fold, with illuminated switch
CO3636-6YServo machine test stand for 1kW machines incl. software ActiveServo (D,GB,F,E)
SE2662-7DCoupling guard with LED lighting for 1kW machines
SE2662-6ARubber coupling sleeve, 1kW
ST7200-7ASybaPro experiment trolley, 3-level, 6 sockets, 1250x1970x800mm
ST8010-4TMonitor holder for flat screen monitor of weight up to 15kg / 33lbs
ST7200-5LProtection cover for three-level experiment trolleys
ST8010-4GKeyboard adapter for flat screen monitor holders
ST8008-8NProtected power distribution for working stations
ST8010-4JMultiple socket outlet, 6 fold, with illuminated switch
ST8000-4JDisplay for Power Generation equipment
SO5126-3RSafety connecting plug 4mm with tap (2x), black, 1000V/32A CAT II
SO5126-3VSafety connecting plug 4mm with tap (2x), blue, 1000V/32A CAT II
SO5126-3WSafety connecting plug 4mm with tap (2x), green/yellow, 1000V/32A CAT II
SO5148-1LSet of safety measurement cables, 4mm (31 leads)

Learning Content in Detail

Participants parameterize each protection function individually, create the associated fault and assess the tripping behavior of the relay.

Parameterizing overvoltage and undervoltage protection

Participants set the characteristics in accordance with ANSI 59/27 and validate the pick-up values during sudden load shedding and during a black start.

Analyzing time-overcurrent protection

Participants test the two-stage monitoring in accordance with ANSI 50/51 and explain why short disconnection times are needed in the event of a short circuit.

Testing unbalanced load protection

Participants apply an unbalanced load, test ANSI 46 and assess the thermal risk to the rotor from negative-sequence currents.

Setting reverse power protection

Participants drive the generator into motor operation and set the time delay in accordance with ANSI 32 to protect against turbine overspeed.

Detecting stator ground faults

Participants simulate an insulation breakdown and check fault detection by vector addition of the line currents.

Features & Applications

The experiments focus on protecting generators in distributed generation plants against impermissible voltage, load and power conditions, and on protecting the rotor against thermal overload due to unbalanced grid loading.
  • Covering thermal and electrical generator faults — The equipment covers critical grid-side and internal scenarios on the same setup: asymmetrical unbalanced load, motoring reverse power and stator ground fault. Participants investigate the phenomena one after another on a single machine.
  • 1 kW power class with limited generator current — The hardware operates in a professional 1 kW power class. In the course, the generator current is limited so that the laboratory environment remains safe and gentle on the machines while the physical principles are retained. Transformer and threshold calculations remain true to practice.
  • Multifunction relay CO3301-5W — The relay digitally monitors generator and grid parameters in accordance with the ANSI standard, for example ANSI 59/27, 46 and 32, and features alarm class logic. It is freely parameterizable and combines control, protection and automatic synchronization in one device.
  • Excitation voltage controller CO3301-5G with de-excitation switch — The controller supplies 7.5 to 200 V at a maximum of 2 A and automatically de-excites the generator in the event of a fault.
  • Four-quadrant test bench CO3636-6Y — The test bench operates statically and dynamically in four quadrants and provides ten driven machine models, including a fan, a pump and a time-dependent load.
  • Industrial software for parameterizing the multifunction relay — The menu-driven configuration software is connected via USB. Participants observe the measured values in real time and link digital signals.
Learners working with RXLea on a tablet at a Lucas-Nuelle training system
RXLea

From Knowledge Comes Capability.

You guide the learning

Where theory and practice go hand in hand.

RXLea brings a new way of learning: project-based, hands-on and clearly structured. Learners solve real-world tasks, while instructors save time on preparation. Interactive modules, smart analytics and real hardware create a modern, efficient learning world.

Hands-on and interactive

Animations, interactive tasks and realistic scenarios build a deep understanding. All content is organized into clear learning paths for focused, hands-on learning.

Digital support

3D assembly animations and digital instructions simplify complex procedures, reduce errors and help learners work more independently.

Visual support

Overview graphics, screenshots and sample animations make the learning world transparent. Photos from the learning packages are also available, including country-specific versions where needed.

Learners using a tablet at an energy training system
RXLea on desktop, laptop and tablet
RXLea Path Creator for building learning journeys
RXLea Navigator showing the learning world
Learn more about RXLea
Newsletter

Stay ahead in
technical training.

Get the latest training systems, product launches and educational insights, delivered directly to your inbox.

Your email address

By subscribing, you agree to our Privacy Policy. You can unsubscribe at any time.

 Please select at least one category before subscribing.
I'm interested in - select all that apply