Item No.: LM8562

Installation tester for protective circuitry according to DIN VDE0100, 0105, 0113 and DGUV

This tester permits operation of all DC, AC and three-phase power supply systems with voltages of 65 up to 100 V and frequencies from 15.4 up to 420 Hz. It complies with all required testing and measurement criteria according to the relevant country standards, e.g. DIN VDE , DGUV, NEN (NL), AS (AUS), ÖNORM (A) and more. With this installation tester, initial as well as repeat tests can be carried out in accordance with DIN VDE 0100 T600, VDE 0105, VDE 0113 and DGUV - regulation 3.

Functions:

• Measurements in AC/DC power systems
• Measurements of the internal system resistance and the earth fault loop impedance with high test current up to 690 V AC/800 V DC without tripping RCD Type A and Type B fuses
• Low ohmic measurements for protective conductor and equipotential bonding conductor with 200 mA, automatic polarity reversal and 25 A
• RCD testing type A, AC, F, B, B+, EV, MI, G/R, SRCDs, PRCDs
• Combined RCD testing with continuously increasing ramp, tripping time, tripping current
• Insulation measurement up to 1000 V with rising ramp
• Testing of RCMs and IMDs
• Measurement of discharge and differential currents
• Measurement of temperature and dampness
• Testing of withstand voltage 2.5 kV AC, 500 VA with PROFITEST PRIME AC standard procedure, ramp function and pulse control mode
• Mains and battery operation (with restricted functionality)

Technical data:

Mains power operation: Auxiliary power supply (mains connection) (85V... 264 V, 16.7 Hz.. 50 Hz ... 400 Hz)
PROFITEST PRIME AC: < 800 VA
Mains disconnection via mains connection socket with mains power disconnect switch
Battery operation: Battery block 3 x Li-ion cells (solidly integrated), type: FEY PA-LN1038.K01.R001
Charging current: 1.9 A
Charging voltage: 12.3 V
Charging time (switch setting ): 1.5 h
Nominal usage range: 9.7 V ... 10.8 V ... 12.3 V
Measurement category power supply: CAT II 300 V
Measurement circuit probe basic measurement functions: 600 V CAT III /300 V CAT IV, (without safety caps): 600 V CAT II)
Measurement circuit HV: 2500 V/200 mA,
Potential HV AC: 2.5 kV
(Fast blowing) Fuses: Mains line connection 2 x M3.15/250V
Data interfaces
Type USB slave for PC connection
Type Bluetooth® for PC connection
Displays: Multiplex display thanks to dot matrix b/w 128 x 128 pixels, illuminated

Dimensions: 50 cm x 41 cm x 21cm (WxDxH)
Weight: approx. 15kg